CRF40 Roof Fan and Filter | Civaux Electric

CIVAUX · ENCLOSURE VENTILATION

Roof ventilation

CRF40 Roof Fan and Filter

Roof-mounted enclosure ventilation with a centrifugal fan. CRF40 extracts warm air at the top of the cabinet and is designed to work with an appropriate inlet filter lower on the enclosure.

Civaux CRF40 roof fan
Free-blowing airflow · no mat860 / 900 m³/h
ProtectionIP22 without mat / IP55 with mat
Panel cut-out258 × 258 mm

DESIGNED AROUND THE PANEL

Ventilation from the roof.

Centrifugal airflow

Roof extraction paired with an appropriate inlet filter lower on the enclosure.

Accessible mounting

Mounting system allows the fan to be secured from inside or outside the enclosure.

Filter access

Accessible filter mat and a polyurethane foam sealing gasket.

SPECIFICATIONS

Technical data.

ParameterSpecification
Available supply voltages230 V AC, 50/60 Hz; 115 V AC, 50/60 Hz
Free-blowing airflow without filter mat (IP22)860 / 900 m³/h
Airflow with filter mat (IP55)675 / 702 m³/h
ProtectionIP22 without mat / IP55 with mat
MotorCentrifugal fan with capacitor motor
Noise level74 dB
Operating temperature−20°C to +70°C

Paired AC figures are in 50/60 Hz order. Specifications reproduced from the 2026 catalogue, printed page 19.

Electrical parameterCatalogue value (50/60 Hz)
Rated current0.51 / 0.55 A
Power105 / 123 W

The catalogue merges the electrical rows across both voltage columns. Confirm the supply-specific current and power before selection.

INSTALLATION

Dimensions.

DimensionSize (mm)
Front width × height400 × 400
Panel cut-out258 × 258
Civaux CRF40 original catalogue dimensions
Original catalogue drawing. Dimensions in millimetres. Printed page 20.

MODEL SELECTION

Ordering options.

Colour230 V AC, 50/60 Hz115 V AC, 50/60 Hz
RAL 7032CRF40.G230Confirm ordering code
RAL 7035CRF40.W230CRF40.W115

G denotes RAL 7032; W denotes RAL 7035. Confirm availability and the complete model code when ordering.

FAN & FILTER

Complete the assembly.

Filter arrangementCatalogue reference
Matching filterCRF40.EX.G / CRF40.EX.W

CRF roof fans require an appropriate inlet filter lower on the enclosure. The references above reproduce the catalogue’s “Exit Filter” row.

Civaux CRF40 roof fan